| Input |
- Nominal input voltage:
95-137 VAC 200-240 VAC
- Input frequency: 47-63Hz
- Input current:
20A max. per breaker 120VAC 16A max. per breaker 230VAC
- Power entry connector: IEC 320 C14 for 15 Amp, C20 for 16 Amp or corded for 20 and 30 Amp
|
| Output |
- Outlet connectors: (8) NEMA 5-15R for 15 Amp or (8) NEMA 5-20R for 20 Amp or (8) IEC 320 C13
- Load current: 15, 20, or 30 Amp max., 16 Amp for 230 VAC, C19 inlet connector non-corded version
|
| Physical |
- Height: 1U, 1.75" (4.44cm)
- Width: 17.25" (43.8cm)
- Depth: 8.25" (20.9cm)
- Weight: 8 lbs. (3.7kg) (15 Amp)
11 lbs. (5.0kg) (20 Amps) 13 lbs. (6.0kg) (30 Amp)
- Convenient 19" rack-mountable or tabletop unit.
|
| Environmental |
- Operating temperature: 0-45°C (32-113°F)
- Operating humidity: 0-95% (non-condensing)
- Operating elevation: 0-10,000ft (0-3000m)
|
|
|
| Communication |
- RS-232: Front panel DB-9F or DB-9M connector
- RS-485/422 rear panel RJ-11
- Telnet with web interface
(when ordered with LAN module)
- Other options available
|
| Unit Combinations |
- (1-Single Inlet) 120V AC input with
(8) NEMA 5-15R for 15 Amp (8) NEMA 5-20R for 20 Amp (8) NEMA 5-15R for 30 Amp outlet connectos.
- (2-Dual Inlet) 120V AC inputs with
(4) NEMA 5-15R for 15 Amp (4) NEMA 5-20R for 20 Amp outlet connectors for each input.
- (1-Single Inlet) 230V AC input with
(8) IEC 320 C13 outlet connectors.
- (2-Dual Inlet) 230V AC inputs with
(4) IEC 320 C13 outlet connectors for each input.
|
| Accessory (optional) |
Environmental Temperature Sensor 72-1021-189 (Hookup wire not supplied) |
| |
| The total input load capacity options available
include, 16 Amp rating with IEC C19 inlet connector
and 30 Amps with and L6-30P cord. The 20 Amp
design is also available with a 5-20P fixed cord-set.
See part numbering information. |
|